How to Read an MCB Time-Current Curve

VUKAR

The tripping time of MCB protection is read as a range at a stated current, using the curve for the exact breaker and its declared conditions. It is not one fixed delay printed beside the rated amperes. Schneider Electric’s worked iC60 example uses a 20 A C-curve breaker at 100 A, or 5 times rated current, and gives a breaking-time range of 0.45–6 seconds. That published example is not a measured result from a VUKAR installation.

A time-current curve relates the current through the protective device to its operating time. Its sloping overload region and near-vertical magnetic region answer different questions. Before following either, identify the product family, rating range, applicable standard, AC or DC basis and reference conditions printed with the graph. A curve letter alone is not a complete graph identity.

Read the current axis before reading the seconds

Many MCB curves put I/In on the horizontal axis. I is the current being assessed; In is the breaker’s rated current. Divide the first by the second. For the documented 20 A example,100 divided by 20 equals 5. You therefore enter the graph at 5, not 100. If another graph uses amperes directly, follow that label instead of performing an unnecessary conversion.

The vertical axis normally identifies time in seconds, often written t(s). Read its scale carefully. On a logarithmic scale, equal distances represent ratios rather than equal additions. The spacing from 0.1 to 1 second can match that from 1 to 10 seconds. A point halfway between decade marks is not their simple arithmetic average. Zoom the manufacturer’s original graph until the ticks and boundary lines are clear.

A useful check is to keep the units beside every number in your notes. Write 100 A,20 A,5 In and seconds in separate fields. This small habit prevents a current multiplier being copied as an ampere value. It also prevents a millisecond value from being treated as a full second when someone transfers a graph reading into a maintenance report.

Assumed breaker rating Same current:100 A Where to enter I/In
16 A 100÷16 6.25
20 A 100÷20 5
32 A 100÷32 3.125

The table is arithmetic only. It does not predict the tripping time of the 16 A or 32 A devices, and it does not approve any of them for a circuit. Its purpose is to show why one measured current occupies different positions on different rated-current curves. Keep the actual breaker’s reference attached to the calculation.

MCB trip time reading interval at five times rated current for the published C20 example
Original interval graphic, not a full trip curve: the published Schneider iC60 C20 example at 100 A=5 In gives 0.45–6 s. The green segment represents that tolerance interval only. Read the actual manufacturer graph and conditions for any other point.

A band has two boundaries

At the chosen current multiplier, trace vertically through the relevant curve band. Read where that vertical line meets the lower and upper time boundaries. These boundaries describe the published operating envelope for the stated conditions. Reporting only the middle of a shaded region discards the tolerance information the drawing was intended to communicate.

The same FAQ links the original Acti 9 tripping-curves and current-limiting document. The attached catalog pages distinguish IEC/EN60898-1 graphs from IEC/EN60947-2 graphs and distinguish rating groups. Select the page before comparing a result. A cropped image that omits its heading can hide exactly the conditions needed to decide whether the band applies.

Disconnected miniature breaker with timing and calculation props for MCB curve reading
Illustrative photograph: the disconnected breaker and props do not show a performed trip-time test or a measured result.

Thermal delay and magnetic response do different jobs

In the overload region, a thermal release responds to heating. For the stated starting conditions, a larger sustained overcurrent generally produces a shorter operating time. This inverse-time behaviour is why a small overload and a much larger fault do not share one universal MCB trip time. The curve is describing the protective device’s response, not a permitted operating schedule for the load.

In the magnetic region, an electromagnetic release responds to a sufficiently large current. The published band identifies the threshold range for that stated device and basis. It is not a promise that every current at the left boundary will produce the fastest possible interruption. Read both boundaries and any qualifying notes. Do not replace the exact graph with an unsourced rule about all B, C or D breakers.

For example, the manufacturer’s attached iC60 IEC/EN60898-1 page for 6–63 A shows C at 5–10 In. Adjacent IEC/EN60947-2 material uses a different presentation and reference temperature. That distinction is easy to lose when an online chart is labelled only “C curve”. The C-type MCB guide explains why the specific series and standard remain part of the interpretation.

Keep a graph reading separate from a fault diagnosis

Suppose a service note says only that a breaker opened after 2 seconds. That observation does not identify the current that flowed during those 2 seconds. It also does not show whether another protective device operated first or whether the timer was started at the same event. The curve cannot be read backwards to produce one certain fault current from that description.

A useful report therefore keeps the observed event and the calculated graph range in different fields. Identify the device that opened, the event used as the timing origin and the evidence available for current. If the current changed during the event, say so. Do not silently compare a changing waveform with a constant-current example and claim the two are the same test. That distinction gives the technician a clear next measurement question.

Check the conditions underneath the graph

Reference temperature is part of the curve’s context. The cited Acti 9 document marks 30°C for its stated IEC/EN60898-1 AC graphs and 50°C for the specified iC60 IEC/EN60947-2 graphs. Those are document-specific reference conditions, not a rule that every breaker sold under a particular standard uses one temperature. Read the actual model’s current technical data when selecting a product.

Previous loading also affects a thermal assessment. A breaker already warm from carrying current is not necessarily in the same starting condition as the documented cold test. Nearby devices, enclosure temperature and installation conditions can matter. The manufacturer’s selection guide treats operating conditions as part of choosing and applying a breaker, rather than treating rated amperes as the whole design.

Keep the graph edition and retrieval date in the record. The FAQ was updated 31 July 2025 and checked 20 November 2026; its attached curves retain their own printed catalog identity. A recently updated web page does not turn an older attachment into a new test report. For a replacement or a new design, obtain the graph that applies to the actual proposed reference.

Illustrative pump observation record used to discuss MCB tripping time evidence
Illustrative photograph: record the start event and measurement method. No actual pump-start trace is claimed.

Use a pump start as a question, not an invented test

A pump can draw a brief starting current before settling to its running current. To assess that start against an MCB curve, the responsible technician needs suitable evidence of both current magnitude and duration, plus the actual device reference and conditions. A nameplate running-current value alone is not a measured startup trace. A controller display reading is not automatically a captured peak.

Ask whether the available measurement method can capture the event being discussed. A slow reading may miss a short peak. Record how the measurement was obtained and what the instrument reports. This article supplies no performed start test and no universal curve recommendation by pump horsepower. The openwell starter comparison helps identify the separate starter documentation needed for the pump application.

The curve does not answer every protection question

Breaking capacity is separate from trip timing. A fast-looking line does not prove that a breaker can interrupt the prospective fault current at the board. Check the declared fault rating, voltage and standard through the complete protective design. The 6 kA-versus 10 kA guide explains that distinction without turning either number into a universal selection.

Likewise, two curves that look separated on screen do not automatically establish short-circuit selectivity. Schneider’s FAQ directs fixed-threshold device comparisons to discrimination tables and explains the need for energy characteristics at short-circuit currents. For very high multiples, the document points to current-limiting information. A simple time-current plot should not be stretched into evidence it does not provide.

Comparing manufacturer MCB time-current documents beside disconnected generic breakers
Illustrative photograph: the blurred charts are scene props, not technical evidence. Use the linked manufacturer document for curve readings.

Save a reading another electrician can reproduce

Record the full breaker reference, curve-page identity, applicable rating group, current and its measurement basis, calculated I/In, lower and upper times, and the graph’s stated conditions. Mark an assumed example as assumed and a manufacturer example as published. Send that record with the original graph to the responsible electrician before requesting a different rating or curve. It makes the next discussion about a reproducible reading instead of an unexplained number of seconds.