C type MCB documentation review illustrated with a generic breaker and planning sheet

Where a C-Curve MCB Fits and How to Read Its Trip Band

VUKAR

A C type MCB can suit a circuit with moderate inrush when its complete trip characteristic also meets the circuit’s protection requirements. The C designation concerns the magnetic-release band; it does not permit continuous operation at several times rated current. For the Schneider C60 EN 60898 example below, that band is 5 to 10 times In. Read the exact manufacturer family and standard, because a different C-labelled device can have a different declared band.

Start with the device reference, rated current and applicable curve. Then compare the load’s current over time with that data. A motor HP figure, the word C16 or one short starting-current number is not enough to confirm selection. The worked examples here use assumed values to explain curve reading. They are not site measurements, performed tests or approved circuit designs.

What the C designation tells you

A thermal-magnetic MCB has two responses. Sustained overloads involve its thermal release. High currents can operate the magnetic release over the declared range. The C letter identifies a characteristic; the rated current remains a separate value. A 16 A device does not become a continuous 80 A device because one boundary of a magnetic band is 5 ×16 A.

The CPWD tripping-characteristics table associates C-curve selection with circuits having surge current, including inductive and motor circuits. That is an application category, not permission to fit C curve to every motor or to change an existing breaker without review. Starting behaviour, conductors and required fault disconnection still have to be checked together.

Reviewing the exact C-curve MCB documentation
Illustrative documentation scene; the generic device is not an identified or tested C-curve model.

Use the curve for the stated family and standard

Schneider’s Multi9 catalog, printed page 148, gives a C60 EN 60898 C-curve magnetic range of 5 to 10 × In. On the same page, its separate IEC 60947-2 section gives 7 to 10 × In for that C60 C characteristic. The manufacturer’s C60 Multi9 curve FAQ also states 7 to 10 for its described AC-rated family. Do not merge these into a single universal claim about every C breaker.

The graph reproduced here is specifically the C60 EN 60898 example. It is not a substitute curve for an unidentified xC60, iC60 or another manufacturer’s device. Look up the exact reference and use its current instructions and declared characteristic for selection. Keep the standard with the curve in the circuit record so a later replacement does not inherit the wrong technical assumption.

Manufacturer C60 C-curve MCB graph under EN 60898 with time and normalized-current axes
Exact manufacturer-curve excerpt: Schneider C60, EN 60898 section, printed page 148. The source specifies cold thermal limits with loaded poles and electromagnetic limits with two loaded poles. Open the image to enlarge; axis meanings and numerical examples appear in accessible text below.
Graph feature Meaning
Horizontal axis I/In Applied current divided by the device’s rated current
Vertical axis t(s) Time in seconds on a logarithmic scale
Two boundary lines A range of operation under the stated conditions, not one promised trip time
Near-vertical lower region The magnetic-release region of this particular characteristic

Read both boundary lines

For an ordinary sustained AC-current point, first calculate I divided by In and locate that ratio on the horizontal axis. Then read upward to the two boundaries and across to the time axis. Keep both limits in view rather than tracing a single convenient line. Check that the source covers the device and conditions being considered before using the result. A simplified current point is not a full starting waveform or a completed coordination study.

The horizontal axis uses a current ratio. If In is 16 A, 80 A corresponds to 5 × In and 160 A to 10 × In. Those calculations locate currents on the example’s magnetic range. They do not establish that the circuit can carry those currents safely or that the device will always trip at the lower boundary. Keep the difference between rated current and operating multiple clear.

The vertical axis is time, and its spacing is logarithmic. Equal distances on the page do not mean equal additions of seconds. The two limit lines form a band rather than a single exact response. Use the source’s stated test conditions. A cold thermal curve should not be treated as a measured prediction for a hot enclosure or a device that has just carried an overload.

When a load profile enters a tolerance band, do not choose a convenient point and call it the trip time. The actual device response depends on the permitted characteristic and conditions. Very short pulses, repeated starts and non-sinusoidal inrush can require additional manufacturer information. In particular, a peak-current figure should not be copied onto a time-current graph as though it were a directly equivalent sustained AC current.

Lighting-load setting for a C-curve MCB inrush review
Illustrative lighting-load setting; the scene does not establish a breaker rating, a curve or a measured inrush.

Do not confuse a multiple such as 10 × In with a 10 kA breaking-capacity marking. For a16 A rating, 10 × In is 160 A. A10 kA marking is 10,000 A of declared fault-interruption capacity at specified conditions; it does not say the device waits for 10,000 A before tripping. Both current-related numbers can appear on a product description, but they answer entirely different questions.

Worked example: sustained heater overload

Assume a fixed heater circuit has a 16 A breaker with the example characteristic, while a hypothetical sustained load draws 20 A. The ratio is 20 ÷ 16 = 1.25 × In. This is a curve-reading exercise showing an overload, not a recommendation to operate the circuit that way. The current is below the5 × In magnetic boundary but that does not remove thermal-overload protection.

The useful next question is how the sustained condition relates to the actual device’s thermal data and the circuit design. Do not use the magnetic5 to 10 band to say “it will not trip until 80 A”. Have the load, cable and protective arrangement assessed. We are not assigning an exact trip time to this hypothetical 1.25 × In condition from a generic image.

Worked example: pump starting current

Now assume a pump-starting study records an applicable equivalent AC current of 96 A for 0.4 s for comparison with a 16 A device using this C60 EN 60898 characteristic. The ratio is 96 ÷ 16 = 6 × In. This assumed point lies within the declared5 to 10 magnetic-current range. That means a reliable no-trip promise cannot be made from the C letter or the amp rating alone.

The designer needs the actual starting profile and the selected manufacturer’s complete data. A pump that starts normally on one arrangement may behave differently after changes to supply, load or starting method. These assumed values are not a motor nameplate, a clamp-meter record or a commissioning result. They only show why duration and the tolerance band matter alongside the starting-current multiple.

Pump starting-profile review for C-curve MCB selection
Illustrative pump scene; the worked starting-current values are assumptions, not measurements from this installation.

Where C-curve MCB selection needs more than inrush

Riding through normal starting current is one side of the decision. The protective arrangement must also interrupt faults as required for the installation. A circuit with a larger magnetic threshold can require a different minimum fault current for the intended rapid operation. The electrician therefore needs the applicable supply, earthing and fault-loop information, not just evidence that the motor starts without tripping.

Also check rated current, breaking capacity at the applicable voltage, poles, cable protection and the intended assembly. A C curve does not identify residual-current protection or a motor-overload relay function. For a pump, the DOL protection selection guide explains why those device roles remain separate. A successful start is not a complete protective-design test.

If an existing MCB trips repeatedly, record when the trip occurs and have the cause investigated. Do not move from B to C, from C to D or to a larger amp rating merely to suppress the symptom. A different characteristic changes part of the protection decision. Device damage, poor connections, moisture, overload or supply conditions can need correction instead of a different curve.

Keep a usable current-profile record

Write the exact breaker reference, rated current, poles, applicable standard and manufacturer curve document on the same record. Add the normal operating current, relevant starting-current information and its duration, plus how those values were obtained. Separate an instantaneous peak, an RMS value and a simplified assumed value. They are not interchangeable evidence for plotting a load against a characteristic.

A qualified electrician should obtain measurements and perform any inspection requiring electrical access using the site’s safe procedure. Do not open a live panel or improvise a fault to see whether a curve is correct. The buyer or operator can collect the existing device reference, equipment documents and a description of when interruptions occur. Keep observation and technical conclusion separate.

Unconnected meter and documentation for a C-curve MCB review
Illustrative record preparation; the meter is unconnected and no displayed value represents a performed test.

Ask for the approved reference and its curve

Give the designer the circuit and load information and ask for the exact approved device, its applicable characteristic and the supporting installation checks. For basic device functions, use the MCB and RCCB explanation. If an alternative is proposed, compare its own data rather than carrying over a curve from the old model.

At handover, retain the selected reference, curve document and relevant test records with the circuit schedule. The next enquiry should be able to identify which C characteristic was actually approved, under which standard, and for which load. A letter on the front is useful only when the complete product and circuit information remain attached to it.