Before you register your device: read this

New VUKAR digital devices run in limited trial mode until they are registered. Registration uses the wrt parameter and a 4-digit code issued by Technical Support — it is not a code you can work out, look up or guess.

Warning: after 7 incorrect code attempts the device locks permanently. A permanently locked device cannot be reset, recovered or reused, and a replacement must be purchased. There are no exceptions once lockout has occurred.

So do not try codes. To register:

  1. Read the 3-digit Device Identification Number from the top display.
  2. Call Technical Support on the number below with that number and your product billing details.
  3. They will issue your unique 4-digit code.
  4. Enter it into the wrt parameter and save.

If you are unsure at any point, stop and call before entering anything. One phone call costs nothing; a locked device costs a new device.

Product Guides

Written guides that answer the questions the manuals get asked about most. No download needed.

Compare models before you buy

Technical Support: +91 6358896254

DM-Universal-V1 Controller Parameters

Full parameter reference for the VUKAR DM-Universal-V1 Custom Motor Protection Device (96 x 96), transcribed from the official user manual (Manual V00). Parameters are grouped in seven menus: SET (Motor Protection), CYC (Cyclic Timer), PRC (System Configurations), CLK (Clock Timer), DS (Day Selection), TIM (ON/OFF Time Schedule) and CCT (Run/Rest Time Schedule). To set a parameter: press UP to increase the value, DOWN to decrease, SET to save and move to the next parameter, MENU to save and exit the menu.

Safety note: parameter settings and wiring changes should be adjusted by a qualified electrician or trained installer only.

Code Parameter What it sets Range Factory default Unit
ol Overload Ampere Maximum current threshold for motor operation. If the motor draws current above this value for the duration set in olt, the system trips to prevent damage. 001.5 - 999.9 100.0 A
olt Overload Trip Delay Time duration the motor is allowed to run above the overload current (ol) before the system trips. 001 - 250 0010 s
dr Dry Run Ampere Minimum current threshold below which the system considers the motor to be running dry (without water). 000.5 - 998.9 000.5 A
drt Dry Run Trip Delay Delay time the motor is allowed to run below the dry run current threshold (dr) before tripping. 0001 - 250 0005 s
hiu High Voltage Cut-off Limit Upper voltage limit. If input voltage exceeds this value continuously, the motor is stopped to protect against overvoltage damage. 140 - 500 500 V
lou Low Voltage Cut-off Limit Lower voltage limit. If input voltage drops below this value continuously, the motor is stopped to prevent malfunction or overheating. 130 - 490 130 V
ast Auto Start Time Delay time after power is restored before the motor starts automatically. 0000 - 0999 0030 s
run Run Timer Maximum continuous runtime duration for the motor. 0000 - 9999 0030 min
rst Rest Timer Mandatory rest period after each motor run before it can start again automatically. 0000 - 9999 0120 min
sdt Not Used Not applicable in the current version of the meter; reserved for future use and development. N/A N/A N/A
trq Torque Timer Time duration for which the green push button is held during motor startup to assist initial torque generation, ensuring a successful and stable motor startup. 000.2 - 060.0 001.0 s
atc Auto Reset Timer Wait time before the system attempts to automatically restart the motor after it stopped on a fault. 0000 - 9990 0003 s
mod Mode of Operation Selects the control mode defining how the motor starts and stops: fully automatic, semi-automatic, or manual. FAUT / SS / ST / DRO ILLEGIBLE (not stated in manual) option
cts CT Coil Selection Selects the appropriate CT configuration based on motor type and ampere range, matching internal calibration with the installed CT type. 1200 / 1201 / 1202 / SQ1 / SQ2 / SQ3 1202 option
mem Memory Enables or disables memory retention of motor ON/OFF state after power failure - whether the device resumes previous motor state after power loss or starts fresh. Yes / No No option
acl Ampere Calibration Fine adjustment of the displayed ampere value to match actual current measurement. 1 - 100 increases display by set percentage; above 100 decreases display by (acl - 100) percent ILLEGIBLE (not stated in manual) %
vcl Voltage Calibration Fine adjustment of the displayed voltage value to match actual voltage measurement. 1 - 100 increases display by set percentage; above 100 decreases display by (vcl - 100) percent ILLEGIBLE (not stated in manual) %
olm Power Failure Overload Lockout Determines whether the system restarts the motor automatically after power resumes if the last shutdown was due to an overload fault. Yes / No No option
wrt User Registration Registers the product for authorized use with a 4-digit code from technical support. Top display shows a 3-digit Device Identification Number; bottom display is used to enter the warranty code. 0000 - 9999 0000 code
dat Calendar Date Sets the current day of month in the internal real-time clock (RTC), required for day-based automation. 01 - 31 01 DD
mon Calendar Month Sets the current month in the internal RTC. 01 - 12 01 MM
yr Calendar Year Sets the current year in the internal RTC; only the last two digits are used. 2025 - 2075 2025 YYYY
day Day of the Week Sets the current day of the week in the RTC (0 = Sunday, 1 = Monday, ..., 6 = Saturday). Required for DAY-based ON/OFF automation. 0 - 6 0 (Sunday) day index
hr Clock Hour Sets the current hour in the RTC using 24-hour format. 00 - 23 00 HH
min Clock Minute Sets the current minute in the RTC. 00 - 59 00 MM
sec Clock Second Sets the current second in the RTC for real-time clock precision. 00 - 59 00 SS
sun / mon / tue / wed / thu / fri / sat Day Selection for Schedule Activation Enables or disables the scheduled ON/OFF or RUN/REST timers for each day of the week. If a day is EN, the device follows the active schedule on that day. EN / DIS EN for all days option
n.01 - n.20 ON Time Schedules 1-20 Scheduled ON times at which the motor starts automatically; 20 independent daily schedules. 00:00 - 23:59 00:00 (Disabled) HH:MM (24-hour)
f.01 - f.20 OFF Time Schedules 1-20 Scheduled OFF times at which the motor stops automatically; paired with the corresponding ON schedules. 00:00 - 23:59 00:00 (Disabled) HH:MM (24-hour)
r.01 - r.20 RUN Time Schedules 1-20 Runtime duration for each scheduled motor ON period - how long the motor remains ON after the corresponding ON time (n.xx) is triggered. 0000 - 9999 0030 min
s.01 - s.20 REST Time Schedules 1-20 Rest duration after the motor completes its run cycle (per r.xx) - the waiting period before the motor can start again per the next ON schedule. 0000 - 9999 0120 min

Note: the factory defaults of hiu (500 V) and lou (130 V) are the disabling values — over- and under-voltage protection is inactive as shipped until the installer sets real cut-off limits (typical: 460 V / 350 V for three phase, 270 V / 200 V for single phase).

DM-Universal-V1 Fault Codes and Reset Procedures

The device shows FLT on the top display and the fault code on the bottom display. Reset procedures as given in the manual:

Display Fault Reset type Reset procedure (per manual)
FLT / oL Overload Manual Reset, Power Reset Manual: press and hold MENU switch for 2 seconds. Power: turn the power OFF and then ON (only if olm parameter value is No).
FLT / dr Dry Run Auto Reset, Manual Reset, Power Reset Auto: fault clears after rst (Rest Timer) duration, only if Cyclic Timer is enabled. Manual: press and hold MENU for 2 seconds. Power: turn the power OFF and then ON.
FLT / hiu Overvoltage Auto Reset Fault resets automatically when voltage falls within the safe window (hiu to lou). To avoid frequent trips, adjust the hiu setting if needed.
FLT / Lou Undervoltage Auto Reset Fault resets automatically when voltage rises back within the safe window. User can lower the lou value temporarily to avoid unnecessary faults.
FLT / SPP Phase Failure Auto Reset Turn the power OFF and isolate the supply first. With the panel isolated and confirmed dead, interchange the R and Y input phase wires to correct the phase sequence — or simply wait until all three phases are restored if the fault is caused by a missing supply phase. This is work for a qualified electrician, not a DIY reset.

DM-Universal-V1 Terminal Connections

Terminal functions from the Digital Meter Connection Diagram (Connection Description, page 9). The device has a 20-terminal block: terminal 2 = C, 3 = NO, 4 = S1, 5 = S2 (top row); 12 = L3, 13 = U1, 14 = SPP, 15 = VLT, 16 = CT2, 17 = CT1, 19 = GND, 20 = +12V (bottom row).

Terminal Function
C Permanent Relay - Common
NO Permanent Relay - Normally Open
S1 Momentary Relay - Common
S2 Momentary Relay - Normally Open
L3 Lower Tank Sensor (when not used, connect with GND)
U1 Upper Tank Sensor (when not used, connect with GND)
SPP Single Phase Preventer, to be connected with SPP pin of Power Supply PCB (when not used, connect with Pin 18)
VLT Voltage Detector, to be connected with AC1 pin of Power Supply PCB
CT1 CT Coil Wire 1
CT2 CT Coil Wire 2
GND GND, connected with Power Supply PCB
+12V +12V DC, connected with Power Supply PCB

All values above are transcribed from the scanned manuals linked at the top of this page. If a value here disagrees with the printed manual supplied with your device, follow the printed manual and contact Technical Support.