MCB Auxiliary Contacts for Status and Trip Indication
VUKARShare
An MCB auxiliary contact reports a breaker state to another circuit. A position contact reports whether the associated breaker is open or closed; a trip-indicating contact reports an operated trip condition. Those are different signals. In Schneider Electric’s documented Acti 9 arrangement, iOF provides position indication and iSD provides trip indication, including operation by a tripping auxiliary. Neither signal, by itself, proves that a pump motor is running or that an installation is safe to touch.
Start by deciding what the receiving lamp, PLC or monitoring system needs to know. “Pump stopped”, “breaker open” and “breaker tripped” are not interchangeable messages. A useful design gives each signal its actual meaning, identifies where it comes from and records what the operator should do when it changes.
Position indication and trip indication answer different questions
Schneider’s published iOF/iSD state comparison distinguishes a manual opening from an automatic trip. In its illustrated arrangement, manually opening the breaker changes the iOF position contact while the iSD remains in its untripped indication. A trip changes the trip indication as well. This is why one generic “MCB alarm contact” label can leave an operator unsure what actually happened.
| Documented event | iOF closed pair | iSD closed pair |
|---|---|---|
| Breaker closed, not tripped | 11–14 | 91–92 |
| Manually opened, not tripped | 11–12 | 91–92 |
| Trip from the represented fault | 11–12 | 91–94 |
| Trip by iMN/iMX auxiliary action | 11–12 | 91–94 |
Likewise, an open position signal does not tell you who opened the breaker or why. To distinguish a maintenance opening from an automatic trip, retain both channels where that information matters. The monitoring screen should use clear labels such as breaker position and trip indication. Do not call every open state a fault just because it interrupts the branch.

Read the changeover contact before designing the signal circuit
The current Schneider instruction sheet PKR1726701-00, page 2/4, shows the iOF changeover terminals 11,12 and 14, and the iSD changeover terminals 91,92 and 94. A changeover contact connects its common to one of two alternatives. In the illustrated manually open, untripped state, the reading key shows 11–12 and 91–92 closed. The accessible table above provides the other documented states.
Our original drawing is a schematic reading key, not a physical terminal layout or a complete control circuit. It does not show a lamp supply, PLC input wiring, fuse choice or an installation’s isolation arrangement. The numbers belong to the named accessory instructions. Do not transfer them to an unidentified module simply because its case is equally narrow.
The accessory contact switches a separate indication circuit; it does not supply that circuit’s operating voltage by itself. A designer must identify the external control supply, receiving device and required protection. Keep mains-rated circuits and low-voltage electronics separated according to the approved design. A spare terminal beside a breaker is not permission to connect a controller input to it.

Choose the accessory for the breaker and the receiving load
Mechanical and electrical compatibility both matter. The current iSD product information names compatible Acti 9 ranges; its fit is not a promise for every DIN-rail MCB or another brand. Check the exact breaker, accessory reference, attachment arrangement and any permitted combination limits. Space on the rail alone does not establish an approved assembly.
There is also a useful current-level distinction in the manufacturer’s replacement guidance. Its A9A26924 replacement notice separates A9A26904 for standard applications from A9A26914 for PLC applications. The latter is specified for 2–100 mA, while the standard reference starts at 100 mA. Selecting the highest headline ampere number can therefore miss the needs of a small electronic input.
The corresponding iSD replacement guidance separates A9A26907 and A9A26917 in the same way. The older A9A26924 and A9A26927 references should not be copied from an old drawing into a new order without the applicable replacement review. The instruction sheet includes the current reference families and their contact-current categories. Match the receiving input’s actual requirements, including its minimum switching conditions.
Read a replacement as a new documented reference
A manufacturer replacement notice identifies an alternative to review; it is not proof that every detail of an old panel can stay untouched. The current product names for A9A26904 and A9A26907 specify bottom connection. The electrician should compare the new instructions with the existing wire routes, available space and terminal access before preparing the work. Preserve the old and proposed references in the revision record.
If a supplier offers another suffix or a combined function, ask for its exact datasheet and schematic. A combined OF/SD accessory can have a function selection that needs to match the signal schedule. Do not copy one contact’s label onto a different function merely to keep the old screen name unchanged.
A headline contact rating is not the whole electrical specification
For example, the A9A26904 product data describes 100 mA–6 A at 240 VAC and 100 mA–3 A at 415 VAC in its stated AC application information. Its DC current capability also changes with voltage. Do not read “6 A” as a universal switching rating at every voltage or for every load type. Keep the voltage, current, AC/DC basis and applicable utilization category together.
A PLC input, an indicator lamp and a relay coil are different receiving loads. Check their documentation rather than assuming they behave the same because they use a similar nominal supply voltage. The contact should operate within its declared range in the approved circuit. If an interposing interface is needed, its type and supply belong in the design; this article does not invent an interface for an unknown panel.
Loss of control power is another separate event. An unlit lamp can result from missing lamp supply, a failed lamp, an open signal path or the breaker state the circuit was designed to show. A single lamp cannot reveal all these causes without additional design provisions. Decide how the monitoring system will represent unavailable indication, rather than treating a dark display as proof of a healthy breaker.

A pump can stop while the breaker stays closed
Consider a planning example in which a contactor normally starts and stops a pump while the branch breaker remains closed. When a tank-full demand stops the contactor, iOF can still indicate breaker closed and iSD can still indicate untripped. That is consistent with the example: the auxiliary contacts are reporting the breaker, not the motor shaft. A genuine motor-running signal needs its own defined evidence.
If the operator manually opens that breaker, the position indication changes; the untripped channel can remain normal in the documented arrangement. If a trip occurs, the trip channel changes too. If a remote tripping auxiliary operated, the same trip channel may change without proving an overcurrent fault. The maintenance log should therefore record the command history and the actual observed trip, instead of guessing the fault cause from one contact.
For a complete pump starter, obtain the installed breaker reference and the starter manufacturer’s approved interface before requesting remote indication. The single-phase openwell starter comparison helps identify the equipment family. It does not establish that the breaker inside a particular VUKAR starter accepts the Schneider accessories discussed here. The OPM-H shown is a complete pump starter. Its built-in MCB does not by itself establish accessory compatibility.
Commission the meaning of each signal
The instruction sheet provides specific test and reset features for the listed auxiliaries. A competent electrician follows those instructions within the installation’s safe procedure and the receiving system’s documented test plan. Do not create a short circuit, overload a pump or bridge protection to test an alarm. This guide reports manufacturer documentation, not a performed commissioning test.
Have the handover record distinguish the expected indication for closed, manually open, tripped and unavailable-control-power states. Record the accessory reference, terminal identification, receiver channel and displayed message. If the installation uses both position and trip signals, verify their different meanings through the approved tests. A screen label should still be understandable to someone who did not write the control program.

Ask for a signal schedule with the quotation
Request the exact breaker and accessory references, manufacturer compatibility evidence, contact rating at the actual circuit conditions, receiver requirements and a labelled signal schedule. Keep position and trip as separate entries when both are needed. Send that specification to the panel designer before purchasing the accessory. It turns a request for an MCB auxiliary switch into a defined indication function with a clear response for the operator.