How to Set Water Level Controller Start and Stop Points
VUKARShare
Water level controller settings should start a filling pump while there is still a useful reserve in the tank and stop it before the overflow level. Choose those points from the tank’s usable volume, household demand and actual filling rate. A low point placed close to the outlet can leave taps dry while the pump waits for permission to start. A high point placed against the overflow gives you little room for movement, switching delay or water still arriving through the inlet.
The distance between the points matters as much as either point alone. It determines how much water is used between starts and how much the pump needs to replace. The examples below are hypothetical calculations, not VUKAR field tests or universal installation dimensions. Have a qualified installer confirm the tank geometry, sensor instructions and control behaviour before changing anything.
Establish the tank’s real boundaries
Start with the lowest level at which the tank can still supply its outlets properly. The internal floor is not automatically that level. An outlet fitted above the floor leaves water behind, and a badly positioned outlet may draw air before the tank looks empty. Water trapped below the useful outlet does not belong in your reserve calculation. Record the outlet height, any sediment allowance and the practical minimum level from the same reference point.
Next identify the overflow entrance. Use its lowest opening into the tank, rather than the height of the pipe outside the tank. The normal pump stop point belongs below this boundary. Leave an allowance that reflects the real installation; tank movement, inlet turbulence and continued delivery after the stop command all deserve attention. There is no single safe centimetre allowance for every tank and pump.
A tank’s advertised capacity also does not tell you the volume between two arbitrary heights. For a rectangular tank with straight vertical walls, horizontal area multiplied by a change in water height gives the corresponding volume. Curved, tapered or horizontal cylindrical tanks need their own volume chart or calculation. Avoid applying a rectangular-tank formula to their changing cross-section.

Turn heights into usable litres
Consider an assumed rectangular tank with an internal floor area of 2 square metres. Suppose its usable outlet minimum is 0.15 metres above the floor, the proposed pump start level is 0.45 metres, the stop level is 1.05 metres and the overflow entrance is 1.20 metres. These are teaching assumptions, not prescribed settings. Every height uses the same internal floor as its reference.
The start-to-stop band is 2 × (1.05 − 0.45) = 1.20 cubic metres, or 1,200 litres. The reserve between the useful minimum and start is 2 × (0.45 − 0.15) = 600 litres. The space between normal stop and overflow is 300 litres. That last figure is spare space, not a replacement for a reliable full-tank stop or an adequately arranged overflow.
| Quantity in this hypothetical tank | Calculation and result |
|---|---|
| Water replaced between normal points | 2 × 0.60 × 1,000 = 1,200 litres |
| Usable reserve below start | 2 × 0.30 × 1,000 = 600 litres |
| Space above normal stop | 2 × 0.15 × 1,000 = 300 litres |
| Assumed reserve duration at 10 litres/minute | 600 ÷ 10 = 60 minutes |
Reserve duration depends on consumption. At an assumed 20 litres per minute, the same 600 litres lasts 30 minutes. The useful observation is that the low point must cover the time until useful refill arrives, not merely the moment when a sensor changes state. A supply window, depleted source or fault can keep the pump stopped after low level requests water.

Understand what your sensor actually adjusts
Separate start and stop electrodes can provide a defined band. ABB’s CM-ENS and CM-ENN instructions describe minimum, maximum and reference electrodes, with filling or emptying behaviour depending on the variant. This is an example of a documented electrode controller, not a wiring guide or a statement that VUKAR uses the same terminals.
A cable float may establish its switching differential through its mounting and permitted movement. Its cable length and fixing position cannot be chosen solely from the litres you want. Follow the exact float’s instructions and check that the float can move without touching the wall, inlet pipe, ladder or another cable. A switch that works in your hand can fail to travel freely inside the tank.
The number of floats also needs interpretation. VUKAR’s current controller family associates a single float arrangement with an overhead tank and a double arrangement with an overhead tank plus a source tank or sump. Two floats therefore do not automatically mean two independently adjustable points in the same tank. Confirm the purpose of each supplied sensor before planning its position.

Choose the refill band around the pump
A wider usable band generally stores more water between normal starts, while a narrower band requests smaller refills. Whether either choice is suitable depends on the pump’s permitted starting frequency, available supply and household demand. The motor manufacturer’s requirements remain relevant; do not make starts more frequent just to keep the tank visually close to full.
For another hypothetical calculation, assume 60 litres per minute reaches the tank with no simultaneous use. Replacing the 1,200-litre band would take 20 minutes. With a steady assumed draw of 10 litres per minute during filling, the net gain is 50 litres per minute and the same rise takes 24 minutes. Delivery into the tank and net tank rise are different measurements.
If the available pumping window is only 15 minutes, changing the high point cannot create the missing water. Review the supply window, refill volume and pump selection. If demand nearly matches incoming flow, tank level may rise very slowly even while the pump is working normally. A timed stop in that situation needs its own assessment rather than repeated increases to a timer.
Setting check: Keep normal level control, source availability and motor protection as separate conditions. A request to fill must not bypass a dry source, overload protection or an unsafe high-level condition. This article gives no terminal substitutions or permission to alter a safety circuit.
Observe a complete cycle before accepting settings
An installer should first confirm the correct filling mode using the exact model documentation. An emptying controller reverses the intended direction of operation. Ask the installer to show which indication means demand is present, which means the motor is actually running and which means a permission is missing. A lit display alone does not prove water is entering the tank.
Observe the falling water level through the intended start point. Record the level at which demand appears and any delay before water arrives. Then observe the rising level through the intended stop point. Check the final settled level after the inlet has stopped delivering. Keep people away from live equipment and use the manufacturer’s approved test method rather than bridging sensor wires.
Repeat the observation under a realistic household draw if that can be done safely. Turbulence near an inlet can move a float differently from quiet water. Record any repeated switching near a threshold, unexpected pause or failure to stop. Investigate the cause before adjusting around it. A jammed float is a mechanical problem, even if moving the setpoint appears to hide the symptom.

Record settings so the next adjustment is useful
Keep a simple commissioning note with tank dimensions, the common height reference, the practical outlet minimum and overflow entrance. Add the actual sensor model, mounting location, normal start and stop levels, observed filling time and what demand occurred during that observation. Date the note. Record any later plumbing change too, including a moved outlet or a new inlet valve. Either can change the meaning of previously satisfactory settings. These details make later changes explainable and help identify a changed water supply or a disturbed sensor.
Use the VUKAR product manual page to match a controller to its own documentation; the downloadable documents are identified by model and language. A listed cyclic timer does not, by itself, establish an adjustable minimum run time, a complete fill-timeout sequence or a daily pumping budget. Ask for the exact feature and its stop behaviour when those functions matter.
Before changing a working installation, write down one target: a sufficient reserve below start, a refill band the pump can manage, or a safer stop below overflow. Change the relevant setting through the approved procedure, then observe the full cycle again. Keep the accepted levels and the reason for them beside the tank record, where the next caretaker can find them.