Pump Won’t Start on Schedule? DEV-K4 Clock and Cyclic Timer Checks
Mohit VekariaShare
If a DEV-K4 pump is not starting on schedule, record the clock event, the selected operating mode and the relevant daily window. Then record what the external starter and motor actually did. The DEV-K4 is a single-phase auto switch with clock and cyclic timers.
Start with what the display shows
| Visible state | What it can mean and what to do |
|---|---|
| Saved start time passes with no motor response | Record the displayed time, active day and mode, and whether a command was visible. Compare the event with the approved schedule and record any later actual start. |
| The display suggests operation, but water is absent | The command and water delivery are separate observations. Note whether the motor actually ran and whether water reached the usual outlet. Report the first missing response. In a supervised return to service, confirm both the motor response and steady delivery. |
| An unfamiliar indication, an unexpected stop or a visible trip | Record the exact characters or lights, the time and the motor state from outside the closed enclosure. Leave protection values as commissioned. If the stop repeats or a breaker has tripped, leave further operation to a qualified electrician. |
Start with the installed unit
Record the model and revision from the label, the motor nameplate and the active mode. Similar panels can have different menus. Use the installed revision’s guide for any setting, its units and the behavior of the selected mode.

Catch the missed event while it is happening
Take one observation at the intended clock time and another when the pump eventually starts, if it does. In each observation record the displayed time, actual time, enabled day, selected mode and what the controller showed. A report that the motor was off at breakfast leaves out whether the clock was wrong, the event was disabled, a rest was still running or protection was active. The two observations give the installer something to compare.
Keep the previous stop in the same log. If the motor ran before the missed event, the elapsed pause and the event time describe two different clocks. Ask the installer whether the selected mode accepts that event while a rest is active. If the setup also uses tank control, add the real tank level and request. Record only conditions that the installed model supports. Use one controlled test event and leave overlapping events and approved protection values alone during the test.
A worked example · DEV-K4
Imagine an installer has set a cyclic operating window and the operator expects a start at its opening. Record the window, panel time and motor state. If the event you expected was a separate programmed clock start, label it separately. A controller indication with a quiet starter gives the electrician a different question from an absent start request. Use the verified installation record to identify the active mode and the appropriate current sensing setup for this 5–200 A model.
Set the clock before using a schedule
A clock event uses a time of day, such as 06:00. RUN and RST are elapsed durations, such as 10 minutes. Read the displayed time, weekday and enabled days together. A saved event can show the correct time yet remain inactive because the wrong day or mode is selected. Begin with one event the operator can safely observe.
Watch the opening and closing of the first window and record the actual behavior. If a pump is already running near closing time, use the installed revision’s instructions to determine how that mode handles the boundary. Write down whether it stopped, completed the current run or waited for a later permission. Test the specific sequence before adding overlapping events or leaving it unattended.
Choose RUN and RST from the water supply
RUN is the elapsed pump-on time. RST is the planned pause between cyclic runs in the selected mode. Choose RUN based on how long the source can deliver a steady flow, the space available where the water goes, and the motor maker’s permitted operating conditions. For RST, consider how long the source needs to recover and any minimum time between starts for the motor.
To estimate starts per hour during an uninterrupted cycle, add RUN and RST in minutes and divide 60 by the total. For example, 10 minutes on and 20 minutes off gives about two planned starts per hour. These are example values. Include any separate starts from other controls, power recovery or fault recovery when the installer reviews the motor’s actual start frequency.

Follow the auto switch to the starter
Treat the auto switch and the motor as separate points in the record. If the installed control circuit permits a start, the starter still has to act and the motor has to run. An indicator on the auto switch shows the state available at that device. It does not tell you everything that happened at the starter or the pump.
Write the auto switch model and the starter model on the same service note. If a command was visible, record the time. On the next line write what you could safely observe at the motor and then when water reached the outlet. An electrician can use the first missing response to identify where to work. Leave control-circuit testing, sensor changes and motor protection settings to them.
Follow the command to the pump
A controller can show a request while the motor is still off. A starter switches motor power when the control circuit permits it. Observe the display, the starter’s visible response and water delivery as separate facts. These observations give the electrician a place to start without asking you to open the enclosure or touch conductors.
If the display shows that the pump should be running but there is no water, write down whether you could see or hear the motor run from a safe location. If the motor runs but delivery is absent or weak, record how long it ran and when the flow changed. Keep the display photo and the times together so the installer can compare them with the actual settings.
Record what happens after an interruption
An automatic restart can have several conditions. If power returns, a permitted start may depend on the mode, restart settings and normal protection conditions. Some configurations also retain earlier timing information. Use the revision guide and ask the installer to explain the behavior for the mode you actually use. Keep the area around the pump and moving parts clear during supervised testing.
If the pump was waiting before an interruption, write down the time of the interruption, the display after power returned and the actual next start if it occurred. Ask the installer to record how a normal cyclic rest differs from a fault recovery wait. Leave restart settings at the approved values until the behavior is understood and tested.
Read the protection indication with the operating record
For overload, note the moment the motor stopped and whether it had reached normal running speed. The configured current response can flag a motor, supply or setup problem. For dry run, record whether water reached the outlet and when delivery weakened. An electrician can compare those events with the installed protection setup and water source.
For a voltage indication, record the time and any interruption you observed. Copy the exact characters on the display. Ask the electrician to use the instructions for the installed revision to identify the indication and decide on recovery. If the fault repeats, leave further operation to the electrician.

Send the installer one usable event record
Use the exact model and revision at the top of your note. Add the symptom and the active operating mode. On the next line, put the actual clock time, elapsed motor time if known, the visible indication and the water condition. State what you expected in the same note. If a detail could not be observed safely, leave it blank and tell the electrician.
Avoid resetting first and trying to reconstruct the event later. The display, tank condition or rest period can change once the equipment is stopped or power returns. If the electrician authorizes another watched test, agree on the expected start and stop in advance and keep the same model record. If a breaker trips, a protection indication returns or the panel appears damaged, leave further operation to the electrician.

Compare like-for-like observations
Use the normal operating record from this installation as your baseline. An older record is useful when it lists the same model revision, selected mode and operating conditions. Put that record beside the new one and mark changes such as a repaired pipe, a different outlet or recent starter service. Note who observed each event and whether the time was measured or recalled.