What Is a Motor Starter? How It Works and the Main Types

Mohit Vekaria

Cover photo: a single-phase VUKAR starter panel during a workshop test.

A motor starter controls when an electric motor gets power and helps protect it from overload. In a basic starter panel, a contactor switches the motor on or off, while an overload relay stops it if it draws too much current for too long. Four common motor starter types and starting methods are DOL, star-delta, soft starters and VFDs.

DOL, star-delta and soft starters are typically for fixed-speed jobs. A VFD can change the motor speed while it runs. Eaton’s guide to electrical starters · ABB’s guide to variable speed drives

Electric motor starter parts and what they do

A basic three-phase direct-on-line panel has two electrical paths. The power circuit carries motor current. The control circuit tells the contactor when to close or open. That is how a push button can start a pump without carrying the current that runs the pump.

  • The contactor is a switch operated by an electromagnet. Its coil moves the main contacts, which connect or disconnect the motor supply.
  • The overload relay watches motor current. If the current stays too high for long enough, the relay opens the control circuit so the contactor releases.
  • A circuit breaker or fuses provide short-circuit protection in the motor power circuit. The correct protective device and its rating depend on the panel and installation.
  • The Start and Stop buttons send commands through the control circuit. A small auxiliary contact on the contactor keeps the motor running after you let go of Start in a conventional push-button circuit.

A normal start can briefly draw much more current than a running motor. An overload relay allows that short rise while protecting the motor from sustained excess current. Eaton’s explanation of overload protection · Schneider Electric’s DOL component guide

Electric motor starter parts in a basic DOL panelFunctional diagram for a conventional three-phase push-button starter

Power path

  1. Three-phase supplyIncoming motor power
  2. Breaker or fusesShort-circuit protection
  3. Main contactsConnect or cut motor power
  4. Overload sensingMonitors motor current
  5. MotorReceives power when contacts close

Control path

  1. Control supplyFeeds the coil circuit
  2. Stop buttonOpens when pressed
  3. Overload trip contactOpens on a trip
  4. Start button or holding contactStart closes briefly. The holding contact stays closed while the coil is on.
  5. Contactor coilMoves the main and holding contacts

The overload sensor trips its control contact. The coil closes the main and holding contacts. Use the manufacturer’s wiring diagram for the exact panel.

Motor starter working principle in one start and stop cycle

Pressing Start on a conventional DOL panel briefly completes the control circuit and energises the contactor coil. The coil pulls the main contacts closed. Full supply voltage reaches the motor, which draws a surge of current as it gets moving. Schneider Electric’s DOL start sequence

Let go of Start and the motor keeps running. When the contactor closed its main contacts, it also closed a smaller auxiliary contact that gives the coil a second path for current around the Start button. Electricians often call it a holding contact. Schneider Electric’s explanation of the holding contact

Press Stop and the coil loses power. A spring opens the main contacts and cuts motor power. An overload trip has the same result because the overload relay opens the control circuit and the contactor drops out. Eaton’s description of how the contactor opens

A power cut drops out the coil and the holding contact opens. When power returns, a basic circuit with a momentary Start button normally waits for someone to press Start again. Schneider Electric’s explanation of momentary push-button control

A digital pump panel may have a separate auto-start mode. On the VUKAR TPM-H, for example, a timer can delay the start after power returns. If you are replacing a pump panel, find out which behaviour the site needs before you choose one. VUKAR TPM-H restart features

Motor starter types compared at a glance

Start with speed. A tank pump that fills and stops may only need switching, while a booster pump that must hold steady pressure as taps open and close may need a drive with a pressure sensor. The table compares what the four motor starter types do at startup and during normal running. ABB’s variable speed drive guide

Method What happens at startup Speed control while running When it fits
DOL Applies full supply voltage at once. Starting current is high. Fixed speed in normal use A compatible motor and supply that can handle a direct start
Star-delta Starts the motor in star to reduce current and torque, then changes to delta. Fixed speed in normal use Six accessible winding terminals, a matching delta voltage rating and a light enough starting load
Soft starter Raises motor voltage gradually at supply frequency. Fixed speed in normal use A motor that needs gentler acceleration and can start with less torque
VFD Adjusts frequency and voltage as it accelerates the motor. Variable speed A process that needs speed control, such as a pump serving changing demand

DOL for a direct start

DOL means direct on line. It gives the motor full supply voltage as soon as the contactor closes. ABB gives a typical starting current of six to eight times rated motor current, with actual values depending on the motor.

If the lights dim each time a pump starts, ask the electrician to measure the voltage dip during starting before selecting a replacement starter. The motor’s HP rating alone gives you little information about that dip. ABB’s Softstarter Handbook · VUKAR’s three-phase DOL starter guide

Star-delta needs the right motor and enough starting torque

The starter first joins the motor windings in star. Each winding gets less voltage, so the motor draws less line current and produces less turning force, or torque. Compared with a direct delta start on the same supply, the ideal star start gives about a third of the starting line current and a third of the starting torque.

If the load is hard to turn, the motor may struggle to pick up speed in star. There can also be a current spike when the starter changes over to delta. ABB’s Softstarter Handbook

The motor must have all six winding terminals accessible and a delta voltage rating that matches the supply. For example, on a 415 V supply, look for a motor approved to run in delta at 415 V. Six terminals alone tell you only that both ends of the windings are accessible. Schneider Electric’s star-delta installation guide · VUKAR’s star-delta starter guide

Soft starter for a gentler start at fixed speed

A soft starter uses electronic switches to raise the voltage gradually as the motor starts. This reduces the starting current and torque compared with a direct start.

Some models can also soften a pump stop, which may reduce water hammer, the pressure surge you sometimes hear as a bang in the pipe. The motor still needs enough torque to get the load moving during the voltage ramp. ABB’s Softstarter Handbook

VFD when the job calls for different speeds

VFD stands for variable frequency drive. It adjusts the voltage and frequency supplied to an AC motor, so it can bring the motor up to speed gradually and then change speed as the job demands.

A booster pump can slow down as demand falls. When you compare types of motor starters for a pump that spends its whole run at one speed, a soft starter may already give you the gentler start you need. ABB’s variable speed drive guide · ABB’s Softstarter Handbook

A tank float changes when the pump starts

A float switch can tell a compatible pump panel to start filling when the water drops and stop when it reaches the set level. The float changes who gives the start command. A DOL panel still applies full supply voltage when its contactor closes, whether the command comes from a float or a push button. VUKAR’s three-phase DOL starter guide · VUKAR’s tank-filling controller guide

When comparing motor starter types for a pump, start with the symptom you want to fix. If the problem is overflow, look at how the tank tells the pump to stop. If the problem is a big voltage dip as the motor starts, have an electrician look at the supply and the starting current before changing the panel. ABB’s Softstarter Handbook

What to send before you buy a starter panel

Take a clear photo of the motor nameplate. Send it with the site supply voltage and a short description of the job, such as filling a tank at a fixed speed or holding pressure as demand changes.

If the panel will start the motor automatically, tell the electrician what you want to happen after a power cut. Have them match the motor’s rated current and the starting method to the installation. Eaton’s motor starter selection guide

See the VUKAR motor starter panel comparison for pump starter options.