DOL Motor Starter Diagram: Power and Control Circuits Explained

Mohit Vekaria

A DOL motor starter diagram shows two circuits. The power circuit carries the current that runs the motor, while the control circuit switches the contactor coil on or off. Once the contactor closes, a direct-on-line starter applies full supply voltage to the motor. The diagrams below show how a conventional three-phase push-button starter works.

Follow the DOL power circuit first

Read from supply to motor. The three incoming lines pass through suitable short-circuit protection and the contactor’s main contacts, followed in this example by overload sensing before they reach the motor. The motor gets power when the contacts close.

The contactor and the protection devices have separate jobs. The contactor switches the motor during normal operation. The overload relay responds when the motor draws too much current for too long. A suitable breaker or fuses provide short-circuit protection for the circuit.

When the motor is stopped, the upstream side of the panel can still be live. Pressing Stop opens the contactor. A qualified electrician must isolate and verify the supply before opening or working inside the panel.

DOL power circuit
  1. Three-phase supply
  2. Breaker or fuses
  3. Main contacts
  4. Overload sensing
  5. Motor

These diagrams explain function. Follow the exact panel and motor drawings for installation.

Read the DOL control circuit at rest

Stop and the overload trip contact are normally closed, so each can pass current when the button sits untouched and the overload relay has yet to trip. Start is normally open. It closes briefly when pressed.

The contactor has a normally open auxiliary contact called a holding contact. It sits on a second path across Start. At rest, Start and the holding contact are both open, so the coil has no complete path.

DOL control circuit
  1. Control supply
  2. Stop · NC
  3. Overload trip · NC
  4. Start · NOHolding contact · NO
  5. Contactor coil
  6. Control return

These diagrams explain function. Follow the exact panel and motor drawings for installation.

What changes when you press Start?

Press Start and current reaches the coil through the Stop and overload contacts. The coil closes the main contacts, supplying the motor. At the same time it closes the auxiliary holding contact.

Release Start. The Start contact opens again, but the closed holding contact keeps the coil energised and the motor running until the control circuit opens or the control supply disappears.

When you press Stop or the overload relay trips, a contact in the control path opens and the coil loses power. The main contacts and holding contact then open.

In a basic momentary push-button circuit, the motor usually waits for a new Start command when power returns. A panel with automatic control can behave differently.

Read the supplied drawing before a motor starter connection

A DOL starter wiring diagram for one model can show a different coil supply or different control devices from another, including a digital controller in the command path of some pump panels. The exact motor and panel documents tell your installer which circuit applies. An overload relay setting should follow the motor nameplate and the protection arrangement shown in the supplied instructions.

If you are replacing a starter, send the installer clear photos of the motor nameplate, the panel model label and the diagram supplied with the panel. Mention whether the pump starts from buttons, a float or another command. That tells them which control path to trace.