Recommended DEV-G3 Settings: Tank-Level Control, Clock and Cyclic Timer
Mohit VekariaShare
For the DEV-G3 recommended parameter settings, establish the borewell’s overhead-tank switching points before adding the DEV-G3 clock window. Then test a permitted fill, a full-tank stop and the documented response at the window boundary.
Start with the installed unit
Write down the model and revision from the unit label, the motor nameplate, the type of starter and the normal operating mode. Keep those details together. Two devices with similar front panels can have different menu options. The correct model guide and the current installation record are the references for any actual setting.
Use the product page to identify available functions and the installed revision’s guide for units, menu names and how the selected mode operates.
If the pump, sensor or operating mode changes, keep the previous record. Mark the date of the change and have the installer observe the revised sequence before relying on automatic operation.

Observe a borewell installation with one float
The listed single-float arrangement uses the overhead tank’s float for the tank signal. Record where the float changes state and how the installer has arranged protection for the water source. A low overhead tank says that the destination needs water. It gives no direct observation of the water available down the borewell.
Watch the water arriving at the tank when the motor starts and again near the end of a normal run. If the flow weakens, note when it changes. Compare it with the reading taken at the first fill or in a different season. The installer can use the record to decide whether to review borewell recovery, the chosen run time or the reason for a protection stop.
Read the real water level and the controller state
Mark the observed low and full switching points with the installer while the sensor is in its normal installed position. Write down the physical water level, the state shown on the controller and when the motor actually starts or stops. If those three observations disagree, keep the evidence and ask the installer to review the level input and the selected mode.
A level sensor can report that the receiving tank needs water. The start can still depend on source conditions, timing and protection. During a supervised test, observe a valid request and the documented full-level stop. If there is a source input, ask the installer to demonstrate its low-water response using the prescribed method while keeping the pump protected.
Set the clock before using a schedule
A clock event uses a time of day, such as 06:00. RUN and RST are elapsed durations, such as 10 minutes. Read the displayed time, weekday and enabled days together. A saved event can show the correct time yet remain inactive because the wrong day or mode is selected. Begin with one event the operator can safely observe.
Watch the opening and closing of the first window and record the actual behavior. If a pump is already running near closing time, use the installed revision’s instructions to determine how that mode handles the boundary. Write down whether it stopped, completed the current run or waited for a later permission. Test the specific sequence before adding overlapping events or leaving it unattended.
What to observe on this model
Use the single overhead float on the listed three-phase borewell arrangement. First observe a permitted fill and the actual full-level stop. Then set one clock window. Compare a low tank just before closing time with a low tank just after it. Write down what the selected mode permits in both cases before adding more clock events.
Use one entry for the clock or day and another for elapsed minutes. Record the selected window, any timer pause and the motor response separately. A later start is easier to explain when the log shows which of those conditions changed first.

Separate a request from permission to start
A low tank can create a request before a clock window opens. Depending on the selected mode, a start can also depend on the state of the water source, any cyclic rest period and protection. Write each condition in a separate line of the event log. That makes it easier to find the actual reason for a delayed start.
Where the controller offers separate operating windows for water-level and cyclic modes, label each saved window by its purpose. Test inside and outside the relevant window with the installer. Ask them to record how your revision treats a low tank at closing time and what it will do when another window opens.
Choose RUN and RST from the water supply
RUN is the elapsed pump-on time. RST is the planned pause between cyclic runs in the selected mode. Choose RUN based on how long the source can deliver a steady flow, the space available where the water goes, and the motor maker’s permitted operating conditions. For RST, consider how long the source needs to recover and any minimum time between starts for the motor.
To estimate starts per hour during an uninterrupted cycle, add RUN and RST in minutes and divide 60 by the total. For example, 10 minutes on and 20 minutes off gives about two planned starts per hour. These are example values. Include any separate starts from other controls, power recovery or fault recovery when the installer reviews the motor’s actual start frequency.
Use the motor and supply limits
Have the electrician match the motor’s nameplate and the controller’s sensing arrangement before setting overload, dry-run or voltage protection. A setting copied from a different pump can be unsuitable even when the pumps have the same horsepower. Ask the electrician to record the approved values, their units and which manual or measurement they used. Keep the previous approved values in the record if a setting needs to be changed.
Observe normal operation from a dry and safe place with the enclosure closed. Changes to wiring, live measurements, current sensing, protection and automatic restart belong with the installer. If a fault reappears, record the indication and stop using automatic operation until the cause has been assessed. Use the product instructions and the applicable electrical safety rules for installation and service.
What to record
| Water and source | Actual tank level or water delivery, and when it changed. |
|---|---|
| Controller | Active mode, saved value or visible indication and its unit. |
| Starter and motor | Actual start and stop, and first permitted restart where applicable. |
Make a two-line event record. In the first line write the expected result and the setting that should produce it. In the second line write the actual time, visible indication and observed water delivery. If an observation is missing, leave that field blank and tell the installer.

Follow the command to the pump
A controller can show a request while the motor is still off. A starter switches motor power when the control circuit permits it. Observe the display, the starter’s visible response and water delivery as separate facts. These observations give the electrician a place to start without asking you to open the enclosure or touch conductors.
If the display shows that the pump should be running but there is no water, write down whether you could see or hear the motor run from a safe location. If the motor runs but delivery is absent or weak, record how long it ran and when the flow changed. Keep the display photo and the times together so the installer can compare them with the actual settings.
Prepare the installation for a watched test
Choose a time when the source has water, the receiving point has room for delivery and the operator can observe from a safe place. Agree with the installer on what counts as a successful start and stop. Use the normal operating controls. Have the installer handle any changes to the electrical circuit or protection settings.
Tell everyone working near the pump when an automatic start could occur. Keep the enclosure closed while observing the display. If the observed behavior differs from the manual or the approved record, stop the test in the normal safe way and write down what happened before any values are changed.
Keep a record another operator can use
Write the model and revision, the motor details, the saved mode and the approved values at the top of the record. Under that, note actual start and stop times, any physical tank level or source condition, the display at the time and the result of the test. If the installed setup uses automatic restart, include the first permitted restart and what triggered it.

Model guide and support
Model or family reference · VUKAR Technical Support
Keep the model label, visible display and motor nameplate ready.