Electrical Power Formula: Calculate Watts for DC, Single-Phase and Three-Phase Loads
Mohit VekariaShare
Calculate electrical power with P = V × I for steady DC, P = V × I × PF for single-phase AC, and P = √3 × V × I × PF for balanced three-phase AC. Use line-to-line voltage and line current in the three-phase formula. Divide watts by 1,000 to get kilowatts.

Choose the formula for your supply
Swipe the table sideways to see more columns.
| Supply | Real power in watts | Inputs to use |
|---|---|---|
| Steady DC | V × I | DC volts and DC amps. |
| Single-phase AC | V × I × PF | RMS supply voltage, RMS current and power factor. |
| Balanced three-phase AC | √3 × V × I × PF | RMS line-to-line volts, RMS line amps and power factor. |
For a predominantly resistive AC load, PF is close to 1. Motors and electronic loads may need a measured PF or a direct real-power reading. With unbalanced or distorted waveforms, use an appropriately configured power meter for total kW.
Eaton guide to AC power and power factor
Worked examples using volts and amps
Single-phase motor example
230 V × 6 A × 0.80 = 1,104 W
This is 1.104 kW of electrical input at the measured load. Two hours at that steady input uses 2.208 kWh.
Balanced three-phase example. At 415 V line to line, 10 A line current and 0.82 PF, input is √3 × 415 × 10 × 0.82 ≈ 5,894 W, or 5.89 kW.
DC example. A steady 24 V load drawing 3 A uses 72 W. This is the load’s DC input. If a mains power supply feeds it, the mains input also includes conversion losses.
Get a useful power estimate for your pump
- Read the nameplate. Confirm whether the motor is single-phase or three-phase. A motor’s rated HP usually describes shaft output.
- Use operating readings. Use voltage, current and PF taken at the same running load. If the load changes, use a meter that records real power or energy over the full cycle.
- Apply your runtime. Multiply average input kW by actual running hours. For a cost estimate, apply the energy rate and account for separate bill charges.
Quick answers
Can I multiply 230 V by amps to get watts?
For a single-phase AC load, that gives volt-amperes. Multiply by PF to get real watts. With PF near 1, the two readings are close.
How do I estimate units for one tank fill?
Measure energy during one fill, or multiply average input kW by the time in hours from start to stop.
To convert between kW, kVA and current, use the electrical power and current converter.