Power Factor Formula: Calculate It from kW, kVA and Current

Mohit Vekaria

Power factor equals real power in kW divided by apparent power in kVA. If a meter reads 7.5 kW and 10 kVA at the same time, the power factor is 0.75. You can also calculate apparent power from voltage and current for a single-phase or balanced three-phase load.

kWReal power drawn by the load.
kVAApparent power based on voltage and current.
Power factorThe fraction of apparent power represented by real power.
Two meters with different bar lengths to represent different readings
Use real power in kW and apparent power in kVA measured at the same time.

Choose the formula for the readings you have

Swipe the table sideways to see more columns.

Power factor formulas by available readings
Readings Power factor calculation
kW and kVA PF = kW ÷ kVA.
Single-phase W, V and A PF = W ÷ (RMS V × RMS A).
Balanced three-phase W, line V and line A PF = W ÷ (√3 × line-to-line RMS V × RMS line A).

Use real electrical input in watts when the denominator is in volt-amperes. Take all readings at the same operating point. A motor’s rated HP is shaft output, so it cannot substitute for measured input kW.

Schneider Electric kVA formulas · Schneider Electric guide to true power factor

How power factor changes motor current

When real power and supply voltage stay the same, a lower power factor means higher current. The example below uses a balanced three-phase 415 V supply and a constant 10 kW load.

10 kW load at 415 V

0.75 PF → 18.55 A • 0.95 PF → 14.64 A

Divide 10,000 W by √3 × 415 V × PF. The supply current in this example falls by about 21%. The load still draws 10 kW of real power.

A plant may benefit from lower cable losses or changes to kVA or power-factor charges. The effect on a bill depends on the tariff and where the correction is installed.

When to calculate correction in kVAR

  1. Measure the load. Record kW and true PF across a normal operating cycle. Check whether low PF occurs on one motor or across the panel.
  2. Estimate reactive power. For a sinusoidal inductive load, correction kVAR = kW × (tan φ₁ − tan φ₂), where each angle is arccos of its power factor. Moving a steady 10 kW load from 0.75 to 0.95 gives about 5.53 kVAR.
  3. Check the installation. Have a qualified designer account for changing load, harmonics and the switchgear before specifying capacitors. Keep conventional correction capacitors off a VFD output unless the drive manufacturer explicitly permits the arrangement.

Eaton power factor correction guide

Quick answers

Can you calculate power factor from amps alone?

No. You also need real input power and enough readings to calculate apparent power, or a meter that displays true PF directly.

Is cos φ always the same as power factor?

For sinusoidal voltage and current, yes. Harmonic distortion can make true PF differ from the displacement factor shown as cos φ.

To estimate reactive power for an inductive load, use the power factor correction calculator.