What Is a Contactor? Working, Terminals and Motor Selection

Mohit Vekaria

A contactor is an electrically operated switch that turns a motor or other load on and off. A small control circuit energises its coil, which closes the larger power contacts. For a motor starter, match the contactor’s motor-duty rating to the motor voltage and current, then match the coil to the control supply.

Power circuitCarries the motor current through the main contacts.
Control circuitEnergises the coil when the starter calls for a run.
Motor protectionUses separate overload and short-circuit protection in the starter.
Separate symbols for a contactor coil and its switching contacts
The coil operates the contacts, which open or close the motor circuit.

How a contactor works

  1. Start command. The control circuit energises the coil.
  2. Motor runs. The coil pulls in the moving contacts. The main contacts close and feed the motor.
  3. Stop command. The coil releases. A spring opens the main contacts and the motor loses its supply.

An auxiliary contact can signal that the contactor has closed or help hold a start command. A motor overload relay can tell the control circuit to drop out when it detects a sustained overload.

How to read the terminals

Swipe the table sideways to see more columns.

Common markings on a three-pole contactor
Marking Role
A1 and A2 Coil terminals. Check the coil voltage, AC or DC type and any polarity marking.
L1, L2, L3 and T1, T2, T3 Typical supply-side and motor-side markings for the three main poles.
13–14 A common marking for a normally open auxiliary contact.
21–22 A common marking for a normally closed auxiliary contact.

Use the diagram printed on the specific device. For example, some DC coils have polarity requirements.

Schneider Electric terminal markings · Schneider Electric DC coil markings

How to select a contactor for a motor

For routine starting and stopping of a squirrel-cage motor, check the manufacturer’s AC-3 motor-duty rating at the actual supply voltage. Frequent inching or plugging calls for a review of a different duty category. Check the available auxiliary contacts and how the contactor coordinates with the starter’s protection devices.

Example for a three-phase pump

415 V motor • 8 A nameplate • 24 V DC control supply

Check a contactor rated at least 8 A for AC-3 at 415 V, with a 24 V DC coil. Also check the switching duty, enclosure temperature and protection combination in the manufacturer’s data.

Schneider Electric AC-1 and AC-3 ratings

Contactor, relay and overload relay

Swipe the table sideways to see more columns.

What each component does
Component Typical job
Motor contactor Switches the motor power circuit.
Control relay Switches signals or smaller control loads within its rating.
Overload relay Detects a sustained motor overload and initiates a stop.

Quick answers

Can a 415 V motor starter use a 24 V coil?

Yes. A starter can use a separate 24 V control supply with a matching coil while its main contacts switch the 415 V motor circuit.

What if the contactor keeps clicking?

Have a technician check the control voltage and the source of the start command. Read the pump starter clicking guide for common symptoms and checks.

If your starter repeatedly pulls in and drops out, read the contactor clicking troubleshooting guide.