Insulation resistance tester beside a disconnected motor on a workbench

Megger Test: Purpose, Procedure and Insulation Resistance Readings

Mohit Vekaria

A megger test measures insulation resistance in megohms using a DC insulation tester. On a motor, it helps detect leakage paths caused by moisture, contamination or damaged insulation. Compare the reading with the motor manufacturer’s criteria and earlier readings taken under comparable conditions. A single reading needs its test voltage, duration and temperature for context.

MΩMegohms. The unit used to report insulation resistance.
Test voltage and timeRecord both because they affect the reading and its interpretation.
TemperatureUse the specified correction or compare under similar conditions.

What an insulation test tells you

Swipe the table sideways to see more columns.

Choose the test that answers your question
Test What it checks
Insulation resistance Leakage paths through insulation, such as between motor windings and the frame.
Winding resistance Electrical resistance in the windings. Comparison can flag imbalance or a connection problem.
Earth-bond continuity Whether the protective bonding path has the required continuity.

The motor, drop cable and joints may all contribute to a low reading when tested together. Testing sections separately helps localise the fault where connections are accessible. A satisfactory insulation resistance reading does not rule out every winding fault, including some interturn faults.

Megger insulation testing guide · Megger motor test functions

What a technician checks before and after the test

  1. Isolate and verify. A qualified technician isolates the motor, secures it against restart and verifies absence of voltage.
  2. Separate sensitive equipment. Disconnect drives and sensitive electronics from the test path using the manufacturer’s procedure. Identify whether the measurement includes the cable, the motor or both.
  3. Test using the specified method. Choose the DC test voltage, connections and test duration for that equipment. Record the motor temperature and conditions with the result.
  4. Discharge and document. After the test, discharge the circuit and verify it is safe before touching terminals or reconnecting equipment. Record the reading and exactly what was tested.

Example manufacturer guidance on separating a drive before insulation testing

Tester, record sheet and magnifying glass icons
Compare the measured insulation resistance with the motor manufacturer’s criteria.

How to read the result

Illustrative trend on one motor

120 MΩ → 85 MΩ → 28 MΩ

If the same section was measured at comparable temperature, voltage and duration, the falling trend deserves investigation. Compare it with the motor maker’s limits and check the cable, terminations and windings before deciding on service.

Ask for the measured MΩ, the test voltage, the duration, the temperature and the part tested. If the pump is below ground, ask whether the reading covers the downhole cable and motor together. That tells you what a repairer can conclude from the result.

Submersible pump repair guide

Quick answers

Is there one pass value for every pump motor?

Use the manufacturer’s criteria for that motor, with the specified test method and temperature basis. A figure from a different motor or test setup may give the wrong conclusion.

Can a multimeter replace a megger test?

A multimeter’s resistance mode uses a much lower test voltage. A qualified technician uses a suitable insulation tester for the specified DC test.

If the motor runs but the starter reports a fault, compare dry-run and overload symptoms.