Energy • Runtime • Cost

Estimate what your water pump costs to run.

Enter motor output power and efficiency to estimate energy use and running cost. Add verified electrical details when you also need an estimated current and kVA.

Step 1

Enter pump usage

Use motor nameplate or verified data.

%

Use the motor nameplate, datasheet or verified test value.

Also estimate current and kVAOptional

Use actual nameplate, manufacturer or measured values. No electrical value is assumed.

Supply phase
V

Three phase: line-to-line voltage. Single phase: supply voltage.

Ratio of active power (kW) to apparent power (kVA).

A

Used for neutral comparison only—not validation.

Step 2

Your estimate

Enter your pump power, runtime and electricity rate.

Fixed charges and taxes are not included.
Which power value should I use?

Use the motor's rated shaft output in hp, kW or W and its efficiency from the nameplate or manufacturer data. The calculator divides output power by efficiency to estimate electrical input power.

Formula and assumptions

Energy per run = input kW × run hours. Monthly energy = energy per run × runs/day × operating days. Cost = kWh × your energy rate. Apparent power = input kW ÷ power factor. Current uses input power ÷ (voltage × power factor) for single phase and input power ÷ (√3 × line voltage × power factor) for three phase.

What this estimate excludes
  • Fixed charges, demand charges, slab changes, taxes, penalties and subsidies.
  • Power variation with voltage, loading, pump head, flow, wear and controls.
  • Different runtime or tariff across seasons.
Nameplate comparison and safety

The comparison only shows the numerical difference between the estimated running current and the current you enter. It does not validate the motor or installation. Do not open or probe live electrical equipment unless you are qualified and using appropriate equipment; direct measurement remains more reliable.

Bureau of Energy Efficiency: electrical power, power factor and motor-loading basicsABB: motor input power and current relationshipsNIST: hp and SI conversion factors